EL32xx | Analog Input Terminals RTD (Pt100, Pt1000, ...) · 0 次阅读

Measured value calculation: calibration, adjustment, scaling

As can be seen in the data flow, the measured value can be manipulated computationally in two places:

  • In the calibration object
    • The manufacturer calibration takes place in the manufacturer part (password protected). The Beckhoff adjustment on the production side ensures that the channel complies with the device specification.
    • In the user part, the user can enter their own gain/offset values.
  • In the scaling object

User scaling, index 0x80n00:01

The user scaling is enabled via index 0x80n00:01, the parameterization via indices

  • 0x80n00:11 offset user scaling
  • 0x80n00:12 gain user scaling

User calibration, index 0x80n00:18, 0x80n00:17

The user calibration is enabled via index 0x80n0:0A, the parameterization via indices

  • 0x80n00:17 user offset calibration
  • 0x80n00:18 user gain calibration

Manufacturer calibration, index 0x80xF

The manufacturer calibration is enabled via index 0x80n0:0B.
Beckhoff reserves the right to parameterize via the device-specific indices of object 0x80nF (see CoE object directory) (see Note Producer Codeword).

Measured value calculation: calibration, adjustment, scaling 1:

Producer codeword

Beckhoff reserves the right to perform basic adjustment of the terminals. The producer codeword is therefore not public.