BK9055 and BK9105 | Bus Coupler for EthernetIP · 0 次阅读

Parameterization of the Bus Coupler using DIP Switches*

*) Firmware version B5 or higher

The following parameterizations can be carried out without using configuration software, with the aid of the DIP switches and the end terminal (KL9010).
This parameterization mode is only active if only one end terminal (KL9010) is inserted. Otherwise, the normal settings apply.

Restoring the manufacturer's settings

  • Switch off the Bus Coupler, and plug in just the end terminal (KL9010).
  • Set all the DIP switches to ON, and switch the Bus Coupler on again.
  • Once the default parameters have successfully been set, the Error LED lights, and the I/O Run and I/O Error LEDs flash alternately.
  • You can then switch the Bus Coupler off, connect the Bus Terminals, and continue as usual.

Setting the Ethernet parameters

  • Switch off the Bus Coupler, and plug in just the end terminal (KL9010).
  • Set all the DIP switches to OFF, and switch the Bus Coupler on again.
  • The I/O RUN and I/O Error LEDs light steadily.
  • Make the desired setting in accordance with the following table.

DIP switch

Parameters

Selection

Setting

Comment

1

Baud Rate

10 MBaud

OFF (0)

 

100 MBaud

ON (1)

Default

2

Auto-Baud-Rate

Disable

OFF (0)

 

Enable

ON (1)

Default

3

Transmission type

Half duplex

OFF (0)

 

Full duplex

ON (1)

Default

  • To accept the values, set DIP switch 10 to ON.
    By flashing the I/O RUN and I/O ERR LEDs the Bus Coupler indicates that it has accepted the parameters.
  • You can then switch the Bus Coupler off, connect the Bus Terminals, and continue as usual.