 | Further notes on installation requirements - If any damage or malfunction occurs during installation or operation, turn off the power supply immediately and return the device to the factory for inspection.
- Mount the device on a DIN rail so that the input terminals are at the bottom of the device.
- Install the device in a housing that provides protection against electrical, mechanical and fire hazards
- Make sure that the wiring is correct by complying with all local and national regulations.
- Use suitable copper cables designed for a minimum operating temperature of
60 °C at ambient temperatures up to +45 °C, 75 °C at ambient temperatures up to +55 °C and 90 °C at ambient temperatures up to +70 °C. - Make sure that all individual strands of a wire are inside the terminal connection.
- Unused screw terminals should be tightened firmly.
- The maximum temperature of the ambient air is +70 °C. The operating temperature corresponds to the ambient air temperature and is defined 2 cm below the device.
- This device is designed for convection cooling and does not require an external fan. Do not obstruct the air circulation. The ventilation grille must not be covered (e.g. by cable ducts)!
- Maintain the following installation distances:
- 40 mm at the top, 20 mm at the bottom and 5 mm on the left and right are recommended if the device continuously runs at more than 50 % of the rated output.
- Increase this distance to 15 mm if the adjacent device is a heat source (e.g., another power supply).
- The distance can be reduced from 5 mm to zero if the device is permanently loaded with less than 50 %.
- The device is designed, tested and approved for branch circuits up to 20 A without an additional protective device.
Use an additional protective device for branch circuits with larger current values. If an external input protection device is used, do not use one smaller than a 10 A B or 6 A C characteristic in order to avoid incorrect triggering of the circuit breaker. - Do not use this device on AC 200 V mains supplies with loads greater than 4.5 A if the application is sensitive to short drops in output voltage during power cuts, even if they are shorter than 20 ms.
- The device is designed as equipment of "Protection Class I" according to IEC 61140.
- Do not use the device without a proper PE (Protective Earth) connection!
|