Interoperability list according to IEC 60870-5-101 (master)

für TwinCAT SPS Bibliothek: IEC 60870-5-101 Zentralstation (master).

Interoperability list according to IEC 60870-5-101 (master) 1:

Version: 1.2
Datum: 07.03.2014

Here you can open/save the compatibility list (zipped PDF): kompatib101master.zip.

Table of contents:

Process information in monitoring direction

Process information in control direction

System information in monitoring direction

System information in control direction

Parameter in control direction

File transfer

  • Basic application functions
    • Station initialization
    • Cyclic data transfer
    • Read procedure
    • Spontaneous transmission
    • Double transmission
    • Station interrogation
    • Clock synchronisation
    • Command transmission
    • Counter interrogation
    • Parameter loading
    • Parameter activation
    • Test procedure
    • File transfer
    • Background scan
    • Telegram run time acquisition
  • Appendix

General Information

This compatibility list refers to functions supported within IEC 870-5-101.

Compatibility of the individual components has to be agreed for individual projects by all parties involved.

Project information

Projekt No.:
________________________________________________________

Project:
________________________________________________________

Responsible:
________________________________________________________

Date:
________________________________________________________

Compatibility

The selected parameters should be marked in the white control fields as follows:

Interoperability list according to IEC 60870-5-101 (master) 2:

Function or ASDU is not used

Interoperability list according to IEC 60870-5-101 (master) 3:

Function or ASDU is used as specified (preferred option)

Interoperability list according to IEC 60870-5-101 (master) 4:

Function or ASDU is used in reverse mode

Interoperability list according to IEC 60870-5-101 (master) 5:

Function or ASDU is used in regular and reverse mode

System or device

Interoperability list according to IEC 60870-5-101 (master) 6:

System definition

Interoperability list according to IEC 60870-5-101 (master) 7:

Specifications for the control station (master)

Interoperability list according to IEC 60870-5-101 (master) 8:

Specifications for the controlled station

Network configuration

Interoperability list according to IEC 60870-5-101 (master) 9:

Point-to-point

Interoperability list according to IEC 60870-5-101 (master) 10:

Multipoint-partyline

Interoperability list according to IEC 60870-5-101 (master) 11:

Multiple point-to-point

Interoperability list according to IEC 60870-5-101 (master) 12:

Multipoint-star

Physical layer

Transmission speed:

Interoperability list according to IEC 60870-5-101 (master) 13:

100 bps

Interoperability list according to IEC 60870-5-101 (master) 14:

2400 bps

Interoperability list according to IEC 60870-5-101 (master) 15:

56000 bps

Interoperability list according to IEC 60870-5-101 (master) 16:

200 bps

Interoperability list according to IEC 60870-5-101 (master) 17:

4800 bps

Interoperability list according to IEC 60870-5-101 (master) 18:

64000 bps

Interoperability list according to IEC 60870-5-101 (master) 19:

300 bps

Interoperability list according to IEC 60870-5-101 (master) 20:

9600 bps

 

 

Interoperability list according to IEC 60870-5-101 (master) 21:

600 bps

Interoperability list according to IEC 60870-5-101 (master) 22:

19200 bps

 

 

Interoperability list according to IEC 60870-5-101 (master) 23:

1200 bps

Interoperability list according to IEC 60870-5-101 (master) 24:

38400 bps

 

 

Link layer

According to this application-related standard, only telegram format FT 1.2, single character 1 and the time monitoring interval are used.

Address field of the link layer:

Interoperability list according to IEC 60870-5-101 (master) 25:

Not available (only balanced transfer)

Interoperability list according to IEC 60870-5-101 (master) 26:

One octet

Interoperability list according to IEC 60870-5-101 (master) 27:

Two octets

Interoperability list according to IEC 60870-5-101 (master) 28:

Structured

Interoperability list according to IEC 60870-5-101 (master) 29:

Non structured

Link layer transfer procedure:

Interoperability list according to IEC 60870-5-101 (master) 30:

Balanced transfer

Interoperability list according to IEC 60870-5-101 (master) 31:

Unbalanced transfer

Telegram length:

Maximum length L

255

In unbalanced mode some ASDU types are send with low (class 2) priority to the control station.

Interoperability list according to IEC 60870-5-101 (master) 32:

Normed asssignment of ASDU type to class 2 data

Type identifier

Cause of transmission

 

 

Interoperability list according to IEC 60870-5-101 (master) 33:

Special assignment of ASDU type to class 2 data

Type identifier

Cause of transmission

 

 

 

 

 

 

 

 

Interoperability list according to IEC 60870-5-101 (master) 34:

An outstation may return class 1 data when polled for class 2 data if there is no class 2 data available (configuration parameter).

Application layer

Transfer mode for application data

According to this application-related standard, only mode 1 (octet with the lowest value first) according to 4.10 IEC 60870-5-4 is used.

Common ASDU address

Interoperability list according to IEC 60870-5-101 (master) 35:

One octet

Interoperability list according to IEC 60870-5-101 (master) 36:

Two octets

Address of the information object

Interoperability list according to IEC 60870-5-101 (master) 37:

One octet

Interoperability list according to IEC 60870-5-101 (master) 38:

Structured

Interoperability list according to IEC 60870-5-101 (master) 39:

Two octets

Interoperability list according to IEC 60870-5-101 (master) 40:

Non structured

Interoperability list according to IEC 60870-5-101 (master) 41:

Three octets

 

 

Cause of transmission

Interoperability list according to IEC 60870-5-101 (master) 42:

One octet

Interoperability list according to IEC 60870-5-101 (master) 43:

Two octets (with origin address).
Preset to 0, if origin address is not available.

Selection of standardised ASDU's

Process information in monitoring direction

Interoperability list according to IEC 60870-5-101 (master) 44:

<1> :=Single-point information

M_SP_NA_1

Interoperability list according to IEC 60870-5-101 (master) 45:

<2> := Single-point information with time tag

M_SP_TA_1

Interoperability list according to IEC 60870-5-101 (master) 46:

<3> := Double point information

M_DP_NA_1

Interoperability list according to IEC 60870-5-101 (master) 47:

<4> := Double point information with time tag

M_DP_TA_1

Interoperability list according to IEC 60870-5-101 (master) 48:

<5> := Step position information

M_ST_NA_1

Interoperability list according to IEC 60870-5-101 (master) 49:

<6> := Step position information with time tag

M_ST_TA_1

Interoperability list according to IEC 60870-5-101 (master) 50:

<7> := Bitstring of 32 bits

M_BO_NA_1

Interoperability list according to IEC 60870-5-101 (master) 51:

<7> := Bitstring of 32 bits with time tag

M_BO_TA_1

Interoperability list according to IEC 60870-5-101 (master) 52:

<9> := Measured value, normalized

M_ME_NA_1

Interoperability list according to IEC 60870-5-101 (master) 53:

<10> := Measured value, normalized value with time tag

M_ME_TA_1

Interoperability list according to IEC 60870-5-101 (master) 54:

<11> := Measured value, scaled value

M_ME_NB_1

Interoperability list according to IEC 60870-5-101 (master) 55:

<12> := Measured value, scaled value with time tag

M_ME_TB_1

Interoperability list according to IEC 60870-5-101 (master) 56:

<13> := Measured value, short floating point value

M_ME_NC_1

Interoperability list according to IEC 60870-5-101 (master) 57:

<14> := Measured value, short floating point value with time

M_ME_TC_1

Interoperability list according to IEC 60870-5-101 (master) 58:

<15> := Integrated totals

M_IT_NA_1

Interoperability list according to IEC 60870-5-101 (master) 59:

<16> := Integrated totals with time tag

M_IT_TA_1

Interoperability list according to IEC 60870-5-101 (master) 60:

<17> := Event of protection equipment with time tag

M_EP_TA_1

Interoperability list according to IEC 60870-5-101 (master) 61:

<18> := Packed start events of protection equipment with time tag

M_EP_TB_1

Interoperability list according to IEC 60870-5-101 (master) 62:

<19> := Packed output circuit information of protection equipment with time tag

M_EP_TC_1

Interoperability list according to IEC 60870-5-101 (master) 63:

<20> := Packed single-point information with status change detection

M_PS_NA_1

Interoperability list according to IEC 60870-5-101 (master) 64:

<21> := Measured value, normalized value without quantity descriptor

M_ME_ND_1

Interoperability list according to IEC 60870-5-101 (master) 65:

<30> := Single-point information with time tag CP56Time2a

M_SP_TB_1

Interoperability list according to IEC 60870-5-101 (master) 66:

<31> := Double-point information with time tag CP56Time2a

M_DP_TB_1

Interoperability list according to IEC 60870-5-101 (master) 67:

<32> := Step position information with time tag CP56Time2a

M_ST_TB_1

Interoperability list according to IEC 60870-5-101 (master) 68:

<33> := Bitstring of 32 bits with time tag CP56Time2a

M_BO_TB_1

Interoperability list according to IEC 60870-5-101 (master) 69:

<34> := Measured value, normalized value with time tag CP56Time2a

M_ME_TD_1

Interoperability list according to IEC 60870-5-101 (master) 70:

<35> := Measured value, scaled value with time tag CP56Time2a

M_ME_TE_1

Interoperability list according to IEC 60870-5-101 (master) 71:

<36> := Measured value, short floating point value with time tag CP56Time2a

M_ME_TF_1

Interoperability list according to IEC 60870-5-101 (master) 72:

<37> := Integrated totals with time tag CP56Time2a

M_IT_TB_1

Interoperability list according to IEC 60870-5-101 (master) 73:

<38> := Event of protection equipment with time tag CP56Time2a

M_EP_TD_1

Interoperability list according to IEC 60870-5-101 (master) 74:

<39> := Packed start events of protection equipment with time tag CP56Time2a

M_EP_TE_1

Interoperability list according to IEC 60870-5-101 (master) 75:

<40> := Packed output circuit information of protection equipment with time tag CP56Time2a

M_EP_TF_1

Process information in control direction

Interoperability list according to IEC 60870-5-101 (master) 76:

<45> := Single command

C_SC_NA_1

Interoperability list according to IEC 60870-5-101 (master) 77:

<46> := Double command

C_DC_NA_1

Interoperability list according to IEC 60870-5-101 (master) 78:

<47> := Regulating step command

C_RC_NA_1

Interoperability list according to IEC 60870-5-101 (master) 79:

<48> := Set point command, normalized value

C_SE_NA_1

Interoperability list according to IEC 60870-5-101 (master) 80:

<49> := Set point command, scaled value

C_SE_NB_1

Interoperability list according to IEC 60870-5-101 (master) 81:

<50> := Set point command, short floating point value

C_SE_NC_1

Interoperability list according to IEC 60870-5-101 (master) 82:

<51> := Bitstring of 32 bits

C_BO_NA_1

Interoperability list according to IEC 60870-5-101 (master) 83:

<58> := Single command with time tag CP56Time2a

C_SC_TA_1

Interoperability list according to IEC 60870-5-101 (master) 84:

<59> := Double commandwith time tag CP56Time2a

C_DC_TA_1

Interoperability list according to IEC 60870-5-101 (master) 85:

<60> := Regulating step command with time tag CP56Time2a

C_RC_TA_1

Interoperability list according to IEC 60870-5-101 (master) 86:

<61> := Set point command, normalized value with time tag CP56Time2a

C_SE_TA_1

Interoperability list according to IEC 60870-5-101 (master) 87:

<62> := Set point command, scaled value with time tag CP56Time2a

C_SE_TB_1

Interoperability list according to IEC 60870-5-101 (master) 88:

<63> := Set point command, short floating point value with time tag CP56Time2a

C_SE_TC_1

Interoperability list according to IEC 60870-5-101 (master) 89:

<64> := Bitstring of 32 bits with time tag CP56Time2a

C_BO_TA_1

System information in monitoring direction

Interoperability list according to IEC 60870-5-101 (master) 90:

<70> := End of initialization

M_EI_NA_1

System information in control direction

Interoperability list according to IEC 60870-5-101 (master) 91:

<100> := Interrogation command

C_IC_NA_1

Interoperability list according to IEC 60870-5-101 (master) 92:

<101> := Counter interrogation command

C_CI_NA_1

Interoperability list according to IEC 60870-5-101 (master) 93:

<102> := Read command

C_RD_NA_1

Interoperability list according to IEC 60870-5-101 (master) 94:

<103> := Clock synchronization command

C_CS_NA_1

Interoperability list according to IEC 60870-5-101 (master) 95:

<104> := Test command

C_TS_NA_1

Interoperability list according to IEC 60870-5-101 (master) 96:

<105> := Reset process command

C_RP_NA_1

Interoperability list according to IEC 60870-5-101 (master) 97:

<106> := Delay acquisition command

C_CD_NA_1

Interoperability list according to IEC 60870-5-101 (master) 98:

<107> := Test command with time tagCP56Time2a

C_TS_TA_1

Parameters in control direction

Interoperability list according to IEC 60870-5-101 (master) 99:

<110> := Parameter of measured values, normalized value

P_ME_NA_1

Interoperability list according to IEC 60870-5-101 (master) 100:

<111> := Parameter of measured values, scaled value

P_ME_NB_1

Interoperability list according to IEC 60870-5-101 (master) 101:

<112> := Parameter of measured values, short floating point value

P_ME_NC_1

Interoperability list according to IEC 60870-5-101 (master) 102:

<113>:= Parameter activation

P_AC_NA_1

File tranfer

Interoperability list according to IEC 60870-5-101 (master) 103:

<120>:= File ready

F_FR_NA_1

Interoperability list according to IEC 60870-5-101 (master) 104:

<121>:= Section ready

F_SR_NA_1

Interoperability list according to IEC 60870-5-101 (master) 105:

<122> := Call directory, select file, call file, call section

F_SC_NA_1

Interoperability list according to IEC 60870-5-101 (master) 106:

<123> := Last section, last segment

F_LS_NA_1

Interoperability list according to IEC 60870-5-101 (master) 107:

<124> := Ack file, ack section

F_AF_NA_1

Interoperability list according to IEC 60870-5-101 (master) 108:

<125>:= Segment

F_SG_NA_1

Interoperability list according to IEC 60870-5-101 (master) 109:

<126> := Directory (blank or X, available only in monitor [standard] direction)

F_DR_TA_1

Type identifier and cause of transmission asignments (station-specific parameters )

The combination of type identifier / cause of transmission is marked as:

Shaded

Function or ASDU are not required.

Empty

Function or ASDU is not used.

Interoperability list according to IEC 60870-5-101 (master) 110:

Only used in standard direction

Interoperability list according to IEC 60870-5-101 (master) 111:

Only used in reverse direction

Interoperability list according to IEC 60870-5-101 (master) 112:

Used in both directions

Cause of transmission

Number

Cause of transmission

<0>

Not used

<1>

Periodic, cyclic

<2>

Background scan

<3>

Spontaneous

<4>

Initialized

<5>

Request or requested

<6>

Activation (ACT)

<7>

Activation confirmation (ACTCON)

<8>

Deactivation (DEACT)

<9>

Deactivation confirmation (DEACTCON)

<10>

Activation termination (ACTTERM)

<11>

Return information caused by a remote command

<12>

Return information caused by a local command

<13>

File transfer

<20..36>

General interrogation

<37..41>

Counter interrogation

<44>

Unknown type identification

<45>

Unknown cause of transmission

<46>

Unknown address of ASDU

<47>

Unknown information object address

Type identification

Cause of transmission

 

<1>

<2>

<3>

<4>

<5>

<6>

<7>

<8>

<9>

<10>

<11>

<12>

<13>

<20..36>

<37..41>

<44>

<45>

<46>

<47>

p
e
r
/
c
y
c

b
a
c
k

s
p
o
n
t

i
n
i
t

r
e
q

a
c
t

a
c
t
c
o
n

d
e
a
c
t

d
e
a
c
t
c
o
n

a
c
t
t
e
r
m

r
e
t
r
e
m

r
e
t
l
o
c

f
i
l
e

i
n
r
o

r
e
q
c
o

u
n
k
n
o
w
n
t
y
p
e

u
n
k
n
o
w
n
C
O
T

u
n
k
n
o
w
n
C
A
A

u
n
k
n
o
w
n
I
O
A

<1>

M_SP_NA_1

 

X

X

 

 

 

 

 

 

 

X

 

 

X

 

 

 

 

 

<2>

M_SP_TA_1

 

 

X

 

 

 

 

 

 

 

X

 

 

 

 

 

 

 

 

<3>

M_DP_NA_1

 

X

X

 

 

 

 

 

 

 

X

 

 

X

 

 

 

 

 

<4>

M_DP_TA_1

 

 

X

 

 

 

 

 

 

 

X

 

 

 

 

 

 

 

 

<5>

M_ST_NA_1

 

X

X

 

 

 

 

 

 

 

X

 

 

X

 

 

 

 

 

<6>

M_ST_TA_1

 

 

X

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<7>

M_BO_NA_1

 

X

X

 

 

 

 

 

 

 

 

 

 

X

 

 

 

 

 

<8>

M_BO_TA_1

 

 

X

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<9>

M_ME_NA_1

X

X

X

 

 

 

 

 

 

 

 

 

 

X

 

 

 

 

 

<10>

M_ME_TA_1

 

 

X

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<11>

M_ME_NB_1

X

X

X

 

 

 

 

 

 

 

 

 

 

X

 

 

 

 

 

<12>

M_ME_TB_1

 

 

X

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<13>

M_ME_NC_1

X

X

X

 

 

 

 

 

 

 

 

 

 

X

 

 

 

 

 

<14>

M_ME_TC_1

 

 

X

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<15>

M_IT_NA_1

 

 

X

 

 

 

 

 

 

 

 

 

 

 

X

 

 

 

 

<16>

M_IT_TA_1

 

 

X

 

 

 

 

 

 

 

 

 

 

 

X

 

 

 

 

<17>

M_EP_TA_1

 

 

X

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<18>

M_EP_TB_1

 

 

X

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<19>

M_EP_TC_1

 

 

X

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<20>

M_PS_NA_1

 

X

X

 

 

 

 

 

 

 

X

 

 

X

 

 

 

 

 

<21>

M_ME_ND_1

X

X

X

 

 

 

 

 

 

 

 

 

 

X

 

 

 

 

 

<30>

M_SP_TB_1

 

 

X

 

 

 

 

 

 

 

X

 

 

 

 

 

 

 

 

<31>

M_DP_TB_1

 

 

X

 

 

 

 

 

 

 

X

 

 

 

 

 

 

 

 

<32>

M_ST_TB_1

 

 

X

 

 

 

 

 

 

 

X

 

 

 

 

 

 

 

 

<33>

M_BO_TB_1

 

 

X

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<34>

M_ME_TD_1

 

 

X

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<35>

M_ME_TE_1

 

 

X

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<36>

M_ME_TF_1

 

 

X

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<37>

M_IT_TB_1

 

 

X

 

 

 

 

 

 

 

 

 

 

 

X

 

 

 

 

<38>

M_EP_TD_1

 

 

X

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<39>

M_EP_TE_1

 

 

X

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<40>

M_EP_TF_1

 

 

X

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<45>

C_SC_NA_1

 

 

 

 

 

X

X

X

X

X

 

 

 

 

 

X

X

X

X

<46>

C_DC_NA_1

 

 

 

 

 

X

X

X

X

X

 

 

 

 

 

X

X

X

X

<47>

C_RC_NA_1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<48>

C_SE_NA_1

 

 

 

 

 

X

X

X

X

X

 

 

 

 

 

X

X

X

X

<49>

C_SE_NB_1

 

 

 

 

 

X

X

X

X

X

 

 

 

 

 

X

X

X

X

<50>

C_SE_NC_1

 

 

 

 

 

X

X

X

X

X

 

 

 

 

 

X

X

X

X

<51>

C_BO_NA_1

 

 

 

 

 

X

X

X

X

X

 

 

 

 

 

X

X

X

X

<58>

C_SC_TA_1

 

 

 

 

 

X

X

X

X

X

 

 

 

 

 

X

X

X

X

<59>

C_DC_TA_1

 

 

 

 

 

X

X

X

X

X

 

 

 

 

 

X

X

X

X

<60>

C_RC_TA_1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<61>

C_SE_TA_1

 

 

 

 

 

X

X

X

X

X

 

 

 

 

 

X

X

X

X

<62>

C_SE_TB_1

 

 

 

 

 

X

X

X

X

X

 

 

 

 

 

X

X

X

X

<63>

C_SE_TC_1

 

 

 

 

 

X

X

X

X

X

 

 

 

 

 

X

X

X

X

<64>

C_BO_TA_1

 

 

 

 

 

X

X

X

X

X

 

 

 

 

 

X

X

X

X

<70>

M_EI_NA_1

 

 

 

X

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<100>

C_IC_NA_1

 

 

 

 

 

X

X

X

X

X

 

 

 

 

 

X

X

X

X

<101>

C_CI_NA_1

 

 

 

 

 

X

X

 

 

X

 

 

 

 

 

X

X

X

X

<102>

C_RD_NA_1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<103>

C_CS_NA_1

 

 

X

 

 

X

X

 

 

 

 

 

 

 

 

X

X

X

X

<104>

C_TS_NA_1

 

 

 

 

 

X

X

 

 

 

 

 

 

 

 

X

X

X

X

<105>

C_RP_NA_1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<106>

C_CD_NA_1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<107>

C_TS_TA_1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<110>

P_ME_NA_1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X

X

X

X

<111>

P_ME_NB_1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X

X

X

X

<112>

P_ME_NC_1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X

X

X

X

<113>

P_AC_NA_1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X

X

X

X

<120>

F_FR_NA_1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X

X

X

X

<121>

F_SR_NA_1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X

X

X

X

<122>

F_SC_NA_1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X

X

X

X

<123>

F_LS_NA_1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X

X

X

X

<124>

F_AF_NA_1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X

X

X

X

<125>

F_SG_NA_1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X

X

X

X

<126>

F_DR_TA_1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Basic application functions

Station initilization

Interoperability list according to IEC 60870-5-101 (master) 113:

Remote initialization

Cyclic data transmission

Interoperability list according to IEC 60870-5-101 (master) 114:

Cyclic data transmission

Read procedure

Interoperability list according to IEC 60870-5-101 (master) 115:

Read procedure

Spontaneous transmission

Interoperability list according to IEC 60870-5-101 (master) 116:

Spontaneous transmission

Double transmission of information objects with cause of transmission spontaneous

The following type identifications may be transmitted in succession caused by a single status change of an information object. The particular information object addresses for which double transmission is enabled are defined in a project specific list.

Interoperability list according to IEC 60870-5-101 (master) 117:

Single point information M_SP_NA_1, M_SP_TA_1, M_SP_TB_1 und M_SP_NA_1

Interoperability list according to IEC 60870-5-101 (master) 118:

Double point information M_DP_NA_1, M_DP_TA_1 und M_DP_TB_1

Interoperability list according to IEC 60870-5-101 (master) 119:

Step position information M_ST_NA_1, M_ST_TA_1 und M_ST_TB_1

Interoperability list according to IEC 60870-5-101 (master) 120:

Bitstring of 32 bits M_BO_NA_1, M_BO_TA_1 und M_BO_TB_1

Interoperability list according to IEC 60870-5-101 (master) 121:

Measured value, normalized valueM_ME_NA_1, M_ME_TA_1, M_ME_ND_1 und M_ME_TD_1

Interoperability list according to IEC 60870-5-101 (master) 122:

Measured value, scaled valueM_ME_NB_1, M_ME_TB_1 und M_ME_TE_1

Interoperability list according to IEC 60870-5-101 (master) 123:

Measured value, short floating point numberM_ME_NC_1, M_ME_TC_1 und M_ME_TF_1

Station interrogation

Interoperability list according to IEC 60870-5-101 (master) 124:

Global

Interoperability list according to IEC 60870-5-101 (master) 125:

Group 1

Interoperability list according to IEC 60870-5-101 (master) 126:

Group 2

Interoperability list according to IEC 60870-5-101 (master) 127:

Group 3

Interoperability list according to IEC 60870-5-101 (master) 128:

Group 4

Interoperability list according to IEC 60870-5-101 (master) 129:

Group 5

Interoperability list according to IEC 60870-5-101 (master) 130:

Group 6

Interoperability list according to IEC 60870-5-101 (master) 131:

Group 7

Interoperability list according to IEC 60870-5-101 (master) 132:

Group 8

Interoperability list according to IEC 60870-5-101 (master) 133:

Group 9

Interoperability list according to IEC 60870-5-101 (master) 134:

Group 10

Interoperability list according to IEC 60870-5-101 (master) 135:

Group 11

Interoperability list according to IEC 60870-5-101 (master) 136:

Group 12

Interoperability list according to IEC 60870-5-101 (master) 137:

Group 13

Interoperability list according to IEC 60870-5-101 (master) 138:

Group 14

Interoperability list according to IEC 60870-5-101 (master) 139:

Group 15

Interoperability list according to IEC 60870-5-101 (master) 140:

Group 16

The allocation of information object addresses to each individual group must be specified in a separate table.

Clock synchronization

Interoperability list according to IEC 60870-5-101 (master) 141:

Clock synchronization

Command transmission

Interoperability list according to IEC 60870-5-101 (master) 142:

Direct command transmission

Interoperability list according to IEC 60870-5-101 (master) 143:

Direct setpoint command transmission

Interoperability list according to IEC 60870-5-101 (master) 144:

Command .selection and execution

Interoperability list according to IEC 60870-5-101 (master) 145:

Setpoint command .selection and execution

Interoperability list according to IEC 60870-5-101 (master) 146:

C_SE ACTTERM used

Interoperability list according to IEC 60870-5-101 (master) 147:

No additional definition

Interoperability list according to IEC 60870-5-101 (master) 148:

Short pulse duration(duration determined by a system parameter in the outstation)

Interoperability list according to IEC 60870-5-101 (master) 149:

Long pulse duration(duration determined by a system parameter in the outstation)

Interoperability list according to IEC 60870-5-101 (master) 150:

Persistent output

Interoperability list according to IEC 60870-5-101 (master) 151:

Supervision of maximum delay in command direction of commands and setpoint commands

 

Maximum allowable delay of commands and setpoint commands

Counter interrogation

Interoperability list according to IEC 60870-5-101 (master) 152:

Counter read

Interoperability list according to IEC 60870-5-101 (master) 153:

Counter freeze without reset

Interoperability list according to IEC 60870-5-101 (master) 154:

Counter freeze with reset

Interoperability list according to IEC 60870-5-101 (master) 155:

Counter reset

Interoperability list according to IEC 60870-5-101 (master) 156:

General counter request

Interoperability list according to IEC 60870-5-101 (master) 157:

Request counter group 1

Interoperability list according to IEC 60870-5-101 (master) 158:

Request counter group 2

Interoperability list according to IEC 60870-5-101 (master) 159:

Request counter group 3

Interoperability list according to IEC 60870-5-101 (master) 160:

Request counter group 4

Interoperability list according to IEC 60870-5-101 (master) 161:

Mode A:Local freeze with spontaneous transmission

Interoperability list according to IEC 60870-5-101 (master) 162:

Mode B:Local freeze with counter interrogation

Interoperability list according to IEC 60870-5-101 (master) 163:

Mode C:Freeze and transmit by counter-interrogation commands

Interoperability list according to IEC 60870-5-101 (master) 164:

Modus D:Freeze by counter-interrogation command, frozen values reported simultaneously

Parameter loading

Interoperability list according to IEC 60870-5-101 (master) 165:

Threshold value

Interoperability list according to IEC 60870-5-101 (master) 166:

Smoothing factor

Interoperability list according to IEC 60870-5-101 (master) 167:

Lower limit value for transmission of measured values

Interoperability list according to IEC 60870-5-101 (master) 168:

High limit value for transmission of measured values

Parameter activation

Interoperability list according to IEC 60870-5-101 (master) 169:

Activation/deactivation of cyclic or periodic transmission of the addressed object

Test procedure

Interoperability list according to IEC 60870-5-101 (master) 170:

Test procedure

File transfer

File transfer in monitoring direction:

Interoperability list according to IEC 60870-5-101 (master) 171:

Transparent file

Interoperability list according to IEC 60870-5-101 (master) 172:

Transmission of event sequences

Interoperability list according to IEC 60870-5-101 (master) 173:

Transmission of disturbance data of protection equipment

Interoperability list according to IEC 60870-5-101 (master) 174:

Transmission of sequences of recorded analog values

File transfer in control direction:

Interoperability list according to IEC 60870-5-101 (master) 175:

Transparent file

Background scan

Interoperability list according to IEC 60870-5-101 (master) 176:

Background scan

Telegram run time acquisition

Interoperability list according to IEC 60870-5-101 (master) 177:

Telegram run time acquisition

Appendix

Further Information