KL401x/KS401x, KL402x/KS402x | Single- and Dual-Channel Analog Output Terminals, Signal range 0 to 20 mA and 4 to 20 mA · 0 次阅读

Basic function principles

The analog output terminals

with a resolution of 12 bits (4095 steps). The output voltage is output electrically isolated from the K-bus.

The supply voltage fed in via the power contacts is used for generating the output current.

The LEDs indicate the operating state of the associated terminal channels.

  • green Run LED:
    • On: Normal operation
    • Off: Watchdog timer overflow has occurred. If no process data are transmitted by the Bus Coupler for 100 ms, the green LEDs go out. The output assumes a user-specified voltage (see Feature register).

Process data input format

In the delivery state the process data are shown in two's complement form (integer -1 corresponds to 0xFFFF). Alternative presentation types can be selected via the feature register (R32).

Output current

Process data

KL4011, KL4012

KL4021, KL4022

dec

hex

0 mA

4 mA

0

0x0000

10 mA

12 mA

16383

0x3FFF

20 mA

20 mA

32767

0x7FFF

Process data

The process data arriving from the Bus Coupler are output to the process:

Y_dac = X

(1.0)

Neither user nor manufacturer scaling is active.

Y_1 = B_h + A_h * X
Y_dac = Y_1

(1.1)

Manufacturer scaling active

Y_2 = B_w + A_w * X
Y_dac = Y_2

(1.2)

User scaling active

Y_1 = B_h + A_h * X
Y_dac = B_w + A_w * Y_1

(1.3)
(1.4)

Manufacturer and user scaling active

Key

Name

Name

Register

X

PLC process data

-

B_h

Manufacturer scaling: Offset

R19

A_h

Manufacturer scaling: Gain

R20

B_w

User scaling: Offset

R33

A_w

User scaling: Gain

R34

Y_dac

Output value for the D/A converter

-

The equations of the straight line are enabled via register R32.