EL5072 | 2-channel displacement sensor interface, inductive, LVDT, RVDT, half bridge · 0 次阅读

Save position value

The latch function enables the current position value (0x60n1:01 "Position") to be stored in a separate process data, independent of the cycle time. This function can be triggered via:

Save position value via digital input ("Enable latch on digital input", index 0x70n0:03

  • Index 0x80n1:1B "Digital input latch polarity" can be used to specify the level at which the position value is to be stored in a separate process data.
    • 0: input disabled
    • 10: positive edge
    • 11: negative edge
  • Index 0x70n0:03 "Enable latch on digital input" = TRUE
  • At the first parameterized edge at the digital input the current position value is stored in index 0x60n1:02 "Latch value".
  • For confirmation the "Latch extern valid" bit in index 0x60n0:0A is set to TRUE.
  • A renewed activation for saving the position value can only take place when index 0x70n0:03 has been set to FALSE.
  • Index 0x80n0:06 "Enable continuous digital input" can be used to specify whether it is necessary to reactivate the command.
    • FALSE:
      The following pulses at the digital input have no influence on the latch value in index 0x60n1:02 "Latch value" if the bit in index 0x70n0:03 is set.
      A new position value can only be written to index 0x60n1:02 "Latch value" when index 0x60n1:0A "Latch extern valid" is FALSE.
    • TRUE:
      The position value 0x60n1:01 "Position" is written to index 0x60n1:02 "Latch value" for each parameterized edge at the digital input.
      Renewed activation of the index 0x70n0:03 is not necessary. The index 0x60n0:0A "Latch extern valid" is set to TRUE on a registered edge for a PLC cycle.
  • The status of the digital input can be recorded via index 0x60n0:08 "Digital input".