Infosys在阅读器中打开 / AI 翻译

KL31x2/KS31x2 | Two Channel Accurate Terminals · 0 次阅读

Process image

The terminals KL3132, KL3162, KL3142, KL3152 KL3172 and KL3148 are represented in the process image with a maximum of 6 bytes of input data and 6 bytes of output data. These are organized as follows:

Format

Input data

Output data

Byte

SB1

CB1

Word

DataIN1

DataOUT1

Byte

SB2

CB2

Word

DataIN2

DataOUT2

Key

SB n: Status byte for channel n
CB n: Control byte for channel n

DataIN n: Input data word channel n
DataOUT n: Output data word channel n

  • Please refer to the Mapping page for the allocation of the bytes and words to the addresses of the controller.
  • The meaning of the control and status bytes is explained in Control and status bytes.
  • In process data mode the analog values are transferred in output data words DataIN1 and DataIN2. Input data words DataOUT1 and DataOUT2 are not used.

Representation of the analog values

The analog input values are represented by the terminals as follows:

KL3132-0000

Voltage

Decimal

Hexadecimal

-10 V

-32768

0x8000

+10 V

+32767

0x7FFF

KL3142-0000

Current

Decimal

Hexadecimal

0 mA

0

0x0000

20 mA

65535

0xFFFF

KL3152-0000

Current

Decimal

Hexadecimal

4 mA

0

0x0000

20 mA

65535

0xFFFF

KL3162-0000

Voltage

Decimal

Hexadecimal

0 V

0

0x0000

10 V

65535

0xFFFF

KL3172-0000

Voltage

Decimal

Hexadecimal

0 V

0

0x0000

2 V

65535

0xFFFF

KL3172-0500

Voltage

Decimal

Hexadecimal

0 V

0

0x0000

500 mV

65535

0xFFFF

KL3172-1000

Voltage

Decimal

Hexadecimal

0 V

0

0x0000

1 V

65535

0xFFFF

KL3182-0000

Voltage

Decimal

Hexadecimal

-2 V

-32768

0x8000

+2 V

+32767

0x7FFF