EK9320 | PROFINET Bus Coupler for EtherCAT Terminals · 0 次阅读

Technical data EK9320

Technical data

EK9320

Task within EtherCAT system

coupling of standard digital and analog EtherCAT Terminals and EtherCAT Box modules to PROFINET RT networks

Protocol

PROFINET RT

Interfaces

2 x Ethernet 100/1000 Mbit/s

Bus interface

2 x RJ 45 (switched)

I/O connection/Terminals

E-bus (EtherCAT Terminals) / ELxxxx, ESxxxx, EPxxxx

Power supply

24 VDC (-15%/+20%)

Input current

120 mA typ. + (total E-bus current)/4

Power contacts

24 VDC max./10 A max.

Power supply I/O terminals

2 A

Max. power loss

4 W

Max size of process data

max. 1440 bytes input and output data

Electrical isolation

500 V (power contact/supply voltage/Ethernet)

Dimensions (W x H x L)

71 mm x 100 mm x 72 mm

Operating/storage temperature

Installation position horizontal

-25°C … +60°C/-40°C…+85°C
see note! **)

Operating/storage temperature

other installation position

-25°C … +55°C/-25…+85°C
see note! **)

Relative humidity

95 % no condensation

Vibration/shock resistance

conforms to EN 60068-2-6/EN 60068-2-27

EMC immunity/emission

conforms to EN 61000-6-2/EN 61000-6-4

Protection rating/installation position

IP20/any

Markings / approvals *)

CE, EAC, UKCA
cULus

*) Real applicable approvals/markings see type plate on the side (product marking).

Technical data EK9320 1:

E-bus current/installation positions **)

- for > 55°C only horizontal installation position, E-bus current 1 A max.
- for -25°C...+55 °C, any installation position, E-bus current 2 A max.

System data

PROFINET (EK9320)

Number of I/O modules

control-dependent

Number of I/O points

control-dependent

Data transfer medium

4 x 2 twisted pair copper cables category 5 (100 Mbit/s)

Cable length

100 m

Data transfer rate

100/1000 Mbit/s

Topology

star wiring, line topology