PS2001-2410-1001 | Power supply 24 V DC, 10 A, 1-phase, AC 100-240 V, EtherCAT · 0 次阅读

Charging batteries

The power supply can be used to charge lead-acid batteries or maintenance-free batteries (SLA or VRLA batteries). Two 12 V batteries connected in series are required.

Instructions for charging batteries:

  • Use only matched batteries when putting 12 V types in series.
  • Ensure that the ambient temperature of the power supply stays below
    • +40°C for mains voltage of AC 120 V or higher and
    • +35°C for a mains voltage of AC 100 V.
  • Use a 15 A or 16 A circuit breaker or a decoupling diode between the power supply and the battery.
  • Ensure that the output current of the power supply is below the allowed charging current of the battery.
  • The reverse current to the power supply is typically 3.5 mA. This reverse current can discharge the battery when the power supply is switched off, unless a decoupling diode is used.
  • Switch the device to "Parallel Use" mode and adjust the output voltage, measured at no load and at the battery end of the cable, very precisely to the end-of-charge voltage.

End-of-charge voltage

27.8 V

27.5 V

27.15 V

26.8 V

Battery temperature

10°C

20°C

30°C

40°C