KL2521/KS2521 | One Channel Pulse Train Output Terminals, RS485 / 24 V DC · 0 次阅读

Register description

The registers can be read or written via the register communication. They are used for the parameterization of the terminal.

R0 to R7: Registers in the internal RAM of the terminal

The process variables can be used in addition to the actual process image. Their function is specific to the terminal.

  • R0 target counter value (low word)
    This register contains the low word of the target counter value.
  • R1 target counter value (high word)
    This register contains the high word of the target counter value.
  • R2 maximum frequency
    This register contains the high word of the target counter value.
  • R3 counter extension high word
    This register contains the overflow value (internal 32-bit extension).
  • R4 to R6: Reserved
  • R7: Command register [0x0000]
  • For a command to be executed, it is first necessary for the user code word, 0x1235, to be entered into register R31.
  • Command 0x7000: Restore Factory Settings
    Entering 0x7000 in register R7 restores the delivery state for the following registers.

R32:

0x0030
0x2010*

(48dec)
(8201dec)

R38:

0x86A0

(34464dec)

R33:

0x0000

(0dec)

R39:

0x0001

(1dec)

R34:

0x0000

(0dec)

R40:

0x03E8

(1000dec)

R35:

0x0000

(0dez)

R41:

0x03E8

(1000dec)

R36:

0xC350
0x2710*

(50000dec)
(10000dec)*

R42:

0x0064

(100dec)

R37:

0x0000

(0dec)

R43:

0x0032

(50dec)

 

 

 

 

 

*) for KL2521-0015

R8 to R15: Registers in the internal ROM of the terminal

The type and system parameters are hard programmed by the manufacturer, and the user can read them but cannot change them.

  • R8: Terminal type
    The terminal type in register R8 is needed to identify the terminal.
  • R9: Software version (X.y)
    The software version can be read as a string of ASCII characters.
  • R10: Data length
    R10 contains the number of multiplexed shift registers and their length in bits.
    The Bus Coupler sees this structure.
  • R11: Signal channels
    Related to R10, this contains the number of channels that are logically present. Thus for example a shift register that is physically present can perfectly well consist of several signal channels.
  • R12: Minimum data length
    The particular byte contains the minimum data length for a channel that is to be transferred. If the MSB is set, the control and status byte is not necessarily required for the terminal function and is not transferred to the control, if the Bus Coupler is configured accordingly.
  • R13: Data type register

Data type register

Meaning

0x00

Terminal with no valid data type

0x01

Byte array

0x02

Structure 1 byte n bytes

0x03

Word array

0x04

Structure 1 byte n words

0x05

Double word array

0x06

Structure 1 byte n double words

0x07

Structure 1 byte 1 double word

0x08

Structure 1 byte 1 double word

0x11

Byte array with variable logical channel length

0x12

Structure 1 byte n bytes with variable logical channel length (e.g. 60xx)

0x13

Word array with variable logical channel length

0x14

Structure 1 byte n words with variable logical channel length

0x15

Double word array with variable logical channel length

0x16

Structure 1 byte n double words with variable logical channel length

  • R14: reserved
  • R15: Alignment bits (RAM)
    The alignment bits are used to place the analog terminal in the Bus Coupler on a byte boundary.

R16 to R30: Manufacturer parameter area (SEEROM)

The manufacturer parameters are specific for each type of terminal. They are programmed by the manufacturer, but can also be modified by the controller. The manufacturer parameters are stored in a serial EEPROM in the terminal, and are retained in the event of voltage drop-out.

These registers can only be altered after a code word has been set in R31.

R16: Hardware version number

Register R16 contains the hardware version of the terminal.

R31 to R47: User parameter area (SEEROM)

The user parameters are specific for each type of terminal. They can be modified by the programmer. The user parameters are stored in a serial EEPROM in the terminal, and are retained in the event of voltage drop-out. The user area is write-protected by a code word.

R31: Code word register in RAM

Register description 1:

Functionality of the code word register

The code word 0x1235 must be entered here so that parameters in the user area can be modified. If any other value is entered into this register, the write-protection is active. When write protection is not active, the code word is returned when the register is read. If the write protection is active, the register contains a zero value.

  • R32: Feature register
    [0x0030]
    [0x2010] for KL2521-0015
    This register specifies the operation modes of the terminal. Thus, for instance, a user-specific scaling can be enabled for the analog I/Os.

Feature bit no.

 

Description of the operation mode

Bit 0…Bit1

-

No function

Bit 2

0

[0] Watchdog timer active
In the delivery state, the watchdog timer is switched on. Either the manufacturer's of the user's switch-on value is output if the watchdog overflows.

Bit 3

1

[0] Signed amount representation
Signed amount representation is active instead of two's complement representation. (-1 = 0x8001).

Bit 4

1

[1] The counter is cleared on a positive edge of the Counter_Clear bit in the control byte (Control.5)

Bit 5

1

[1] Ramp function active

Bit 6

0/1

[0] Ramp base frequency

  • 0:10 Hz / s
  • 1: 1000 Hz / s

Bit 7

0/1

[0] Input mode

  • 0: relative
  • 1: direct

Bit 8

0/1

[0] Behavior when watchdog triggered

  • 0: Manufacturer's switch-on value
  • 1: User switch-on value

Bit 9

1

[0] Travel distance control active

Bit 10

0/1

[0] Counter

  • 0: delete
  • 1: set

Bit 11…12

-

No function

Bit 13…15

Pos. logic

Neg. logic

[000] Operation mode

Range of values

000

100

Frequency modulation

0 - 500 kHz

001

101

Pulse-direction control

010

110

Incremental encoder

  • R35: User switch-on value
    If the user switch-on value has been enabled with bit R32.8 of the feature register, the terminal sets its output to the user switch-on value in place of the manufacturer switch-on value on the occurrence of a system reset or a watchdog timer overflow (terminal has not received any process data for 100 ms).
  • R36: Base frequency 1 (low word)
    This register contains the low word of the base frequency 1.
    The base frequency 1 is used if
    • the ramp function is deactivated and
    • the Frequency_Selection bit (Control.0) is 0.
  • R37: Base frequency 1 (high word)
    This register contains the high word of the base frequency 1.
    The base frequency 1 is used if
    • the ramp function is deactivated and
    • the Frequency_Selection bit (Control.0) is 0.
  • R38: Base frequency 2 (low word)
    This register contains the low word of the base frequency 2.
    The base frequency 2 is used if
    • the ramp function is deactivated and
    • the Frequency_Selection bit (Control.0) is 1.
  • R39: Base frequency 2 (high word)
    This register contains the high word of the base frequency 2.
    The base frequency 2 is used if
    • the ramp function is deactivated and
    • the Frequency_Selection bit (Control.0) is 1.
  • R40: Ramp time constant (rising)
    The ramp gradient for starting can be set in register 40 with a accuracy of 10 or 1000 Hz/s (Feature.6).
  • R41: Ramp time constant (falling)
    The ramp gradient for stopping can be set with an accuracy of 10 or 1000 Hz / s (Feature.6) using register 41.
  • R42: Frequency factor (direct input, digit x 10 mHz)
    This register contains the frequency factor. If the frequency is entered directly (Feature7 = 1), the process data are multiplied by the frequency factor (see Process data).