Infosys在阅读器中打开 / AI 翻译

PS2001-2410-0000 | Power supply 24 V DC, 10 A, 1 phase, AC 100-240 V · 0 次阅读

Charging batteries

The power supply can be used to charge lead-acid batteries or maintenance-free batteries (SLA or VRLA batteries). Two 12V batteries connected in series are required.

Instructions for charging batteries:

  • Set the output voltage (measured at no load and at the end of the battery cable) very precisely to the end-of-charge voltage.

End-of-charge voltage

27.8V

27.5V

27.15V

26.8V

Battery temperature

10°C

20°C

30°C

40°C

  • Use a 15A or 16A circuit breaker (or a decoupling diode) between the power supply and the battery.
  • Make sure that the output current of the power supply is below the permissible charging current of the battery.
  • Only use matching batteries when connecting 12V types in series.
  • Make sure that the ambient temperature of the power supply remains below 40°C.
  • The reverse current to the power supply (battery discharge current) is typically 3.5mA when the power supply is switched off (except when using a decoupling diode).