PS2001-2420-1001 | Power supply 24 V DC, 20 A, 1-phase, AC 100-240 V, EtherCAT · 0 次阅读

Parallel use for redundancy

Recommendations for the construction of redundant power supply systems:

  • Power supplies that contain a DC-OK signal contact are best suited for the construction of redundant power supply systems.
    • Use this DC-OK signal contact to monitor the individual power supplies.
    • For the power supplies with EtherCAT (e.g. PS2001-2420-1001) the DC-OK bit can be used for monitoring.
  • Use separate grids for each power supply whenever possible.
  • It is recommended to set the output voltages of all devices to the same value (±100 mV) or to leave them at the factory setting.
  • In addition, parallel use must be enabled via the "PSU Features" object in index 0x8001:01 "Parallel use", see chapter "Parallel Use".