The fast PLC task

Here you can unpack the complete PLC sources: TutorialSample.zip

Add the following PLC code to the declaration part of P_SerialComm_HighSpeed:

PROGRAM P_SerialComm_HighSpeed
VAR
     fbSerialLineCtrl    : FB_IEC870_SerialLineCtrl := (
                Mode        := SERIALLINEMODE_PC_COM_PORT, (*SERIALLINEMODE_KL6_5B_STANDARD *)
             Baudrate        := 19200,
                NoDatabits      := 8,
                Parity      := PARITY_EVEN,
                Stopbits        := 1,
                Handshake       := HANDSHAKE_NONE,
                ContinousMode   := FALSE );

    serial_in           AT%IB4000       : PcComInData;
    serial_out      AT%QB4000       : PcComOutData;

    KL6_in      AT%IB4100       : KL6inData5B;
    KL6_out     AT%QB4100       : KL6outData5B;

    hSerial     : T_HSERIALCTRL;
END_VAR

and the instance is called in the program part:

fbSerialLineCtrl(       pComIn      := SEL( fbSerialLineCtrl.Mode = SERIALLINEMODE_KL6_5B_STANDARD, ADR( serial_in ), ADR( KL6_in ) ),
                    pComOut     := SEL( fbSerialLineCtrl.Mode = SERIALLINEMODE_KL6_5B_STANDARD, ADR( serial_out ), ADR( KL6_out ) ),
                    SizeComIn           := SEL( fbSerialLineCtrl.Mode = SERIALLINEMODE_KL6_5B_STANDARD, SIZEOF( serial_in ), SIZEOF( KL6_in ) ),
                    hSerial     := hSerial );

You can find a Twincat System Manager configuration fitting to the PLC on the example overview page.

Communication via standard PC COMx interface

  • In this case the mode parameter is set to the value: SERIALLINEMODE_PC_COM_PORT.
  • At the TwinCAT System Manager the serial_in and serial_out variables are bound to the corresponding IO variables of the serial interface.
  • The interface will and has to be configured within the TwinCAT System Manager (Baudrate, Parity etc.). Other communication parameters at the FB_IEC870_SerialLineCtrl function block are not relevant at this mode.

Communication via serial Beckhoff Bus Terminals KL6xxx

  • In this case the mode parameter is set to the value: SERIALLINEMODE_KL6_5B_STANDARD.
  • At the TwinCAT System Manager the KL6_in and KL6_out variables are bound to the corresponding IO variables of the serial terminal KL6xxx.
  • The interface is configured within the TwinCAT PLC by the instance of the FB_IEC870_SerialLineCtrlfunction block. Communication parameters like baud rate, parity etc. must be set via this function block.

Communication via serial Beckhoff Bus Terminals EL6xxx

PROGRAM P_SerialComm_HighSpeed
VAR
    fbSerialLineCtrl : FB_IEC870_SerialLineCtrl := ( Mode := SERIALLINEMODE_EL6_22B );

    EL6_in AT%IB4100 : EL6inData22B;
    EL6_out AT%QB4100 : EL6outData22B;
    hSerial : T_HSERIALCTRL;
END_VAR
fbSerialLineCtrl( pComIn := ADR( EL6_in ),
        pComOut := ADR( EL6_out ),
        SizeComIn := SIZEOF( EL6_in ),
        hSerial := hSerial );
  • In this case the mode parameter is set to the value: SERIALLINEMODE_EL6_22B.
  • At the TwinCAT System Manager the EL6_in and EL6_out variables are bound to the corresponding IO variables of the serial terminal EL6xxx.
  • The interface will and has to be configured within the TwinCAT System Manager (Baudrate, Parity etc.). Other communication parameters at the FB_IEC870_SerialLineCtrl function block are not relevant at this mode.