| Fieldbus connection for CANopen CX1500-FB510 |
ADS Services
Local process image task 1 port 800 or port 801
Data can be read from and written to the local process image. If it is necessary for outputs to be written, it is important to ensure that they are not used by the local PLC, because the local controller will overwrite these values. The data is not associated with a watchdog, and therefore must not be used for outputs that would have to be switched off in the event of a fault.
Index group | Meaning | Index offset (value range) |
|---|---|---|
0xF020 | Inputs | 0...2047 |
0xF030 | Outputs | 0...2047 |
0x4020 | Flags | 0...4095 |
ADS services
AdsServerAdsState
Data type (read only) | Meaning |
|---|---|
String | Start - the local PLC is running Stop - the local PLC is stopped |
AdsServerDeviceState
Data type (read only) | Meaning |
|---|---|
INT | 0: Start - the local PLC is running 1: Stop - the local PLC is stopped |
AdsServerType
Data type (read only) | Meaning |
|---|---|
String | BX PLC Server |
Register port 100
The ADS port number in the Bus Terminal Controller for register communication is fixed, being set at 100.
Index group | Index offset (value range) | Meaning | |
|---|---|---|---|
Hi-Word | Low Word | ||
0 [READ ONLY] | 0...127 | 0...255 | Registers in the Bus Coupler High word, table number of the Bus Coupler Low word, register number of the table |
1...255 | 0...3 | 1...255 | Register of the Bus Terminal High word, channel number Low word, register number of the Bus Terminal |