Infosys在阅读器中打开 / AI 翻译

EPxxxx | Industrial housing · 0 次阅读

Process image

AI Inputs Channel 1

Process image 1:

The data for the first analog channel can be found under AI Inputs Channel 1.

  • Underrange: Value of the analog input is less than 0/4 mA or -10/0 V
  • Overrange: Value of the analog input is greater than 20 mA or +10 V
  • Limit 1: with activated limit 1 (object 0x80x0:07 = 1) means
    1: value less than limit 1 (set in object 0x80x0:13)
    2: value greater than limit 1 (set in object 0x80x0:13)
    3: value equal to limit 1 (set in object 0x80x0:13)
  • Limit 2: with activated limit 2 (object 0x80x0:08 = 1) means
    1: value less than limit 2 (set in object 0x80x0:14)
    2: value greater than limit 2 (set in object 0x80x0:14)
    3: value equal to limit 2 (set in object 0x80x0:14)
  • Error: This bit is set if overrange or underrange was detected.

AI Inputs Channel 2

The data of the second analog channel have the same structure as those of the first channel.

AO Outputs Channel 3

Process image 2:

The data for the third analog channel can be found under AO Outputs Channel 3.

AO Outputs Channel 4

The data of the forth analog channel have the same structure as those of the third channel.