BK1120, BK1150, BK1250 | Ethernet Bus Coupler for K-Bus Terminals · 0 次阅读

EtherCAT wiring

The cable length between two EtherCAT devices must not exceed 100 m.

Cables and connectors

For connecting EtherCAT devices only Ethernet cables that meet the requirements of at least category 5 (CAt5) according to EN 50173 or ISO/IEC 11801 should be used. EtherCAT uses 4 wires for signal transfer.

EtherCAT uses RJ45 connectors. The pin assignment is compatible with the Ethernet standard (ISO/IEC 8802-3).

Pin

Color of conductor

Signal

Description

1

yellow

TD +

Transmission Data +

2

orange

TD -

Transmission Data -

3

white

RD +

Receiver Data +

6

blue

RD -

Receiver Data -

Due to automatic cable detection (auto-crossing) symmetric (1:1) or cross-over cables can be used between EtherCAT devices from Beckhoff.

The following Beckhoff cables and connectors are suitable for application in EtherCAT systems:

  • ZB9010 (Industrial Ethernet/EtherCAT cable, fixed installation, CAT 5e, 4-core)
  • ZB9020 (Industrial Ethernet/EtherCAT cable, suitable for drag chain applications CAT 5e, 4-core)
  • ZS1090-0003 (RJ45 connector, 4-pin, IP 20, field-configurable)
  • ZS1090-0005 (RJ45 connector, 8-pin (suitable for GigaBit), IP20, field-configurable)
  • ZK1090-9191-0001 (0.17 m EtherCAT patch cable)
  • ZK1090-9191-0005 (0.5m EtherCAT patch cable)
  • ZK1090-9191-0010 (1.0m EtherCAT patch cable)
  • ZK1090-9191-0020 (2.0m EtherCAT patch cable)
  • ZK1090-9191-0030 (3.0m EtherCAT patch cable)
  • ZK1090-9191-0050 (5.0m EtherCAT patch cable)

E-bus supply

Note

Attention! Malfunction possible!

The same ground potential must be used for the E-bus supply of all EtherCAT terminals in a terminal block!