Infosys在阅读器中打开 / AI 翻译

BC8050 and BC8150 | Bus Terminal Controller with RS485 or RS232 Interface · 0 次阅读

Diagnostics

State of the K-bus

An internal bus or Bus Terminal error is indicated in the K-Bus state. A more precise fault description can be obtained via a function block (in preparation). To this end, link the "K-Bus state" variable with your PLC program.

Diagnostics 1:
State of the K-bus

Error bit

Description

Error type

0

No error

No ERROR.

Bit 0

K-bus error

ERROR

Bit 2

K-Bus is re-triggered

NOTE

Reading K-bus state by ADS

In default or TwinCAT configuration the fieldbus state can be read via ADSREAD.

Parameter ADSREAD function block

Description

NetID

local – empty string

Port

1

IndexGroup

16#0006

IndexOffset

16#000C_9000

LEN

1