Lookup table (0x80n1:21 “lookup table length”)

Using the lookup table offers the option to perform a transformation of the input values within the terminal. In the task cycle the terminal uses lookup values to return a corresponding predefined output value for each input value. This allows reconciliation of non-linearities in the signal sequence.

  • The lookup table is enabled via index 0x80n0:0B "Enable lookup table"
  • The total number of lookup values to be used is entered in index 0x80n1:21 "Lookup table length".
    A maximum of 40 values can be entered (0x80n1:21 = 40dec).
    This corresponds to 20 lookup values with 20 X/Y value pairs.
  • The respective X and Y value pairs are to be entered in object 0x80n5 "IND Scaler Settings Ch.n". Note the following regarding the entries in the lookup table:
    • The odd subindices (1, 3, 5, ...) refer to the corresponding X-values, i.e. the values measured by the sensor.
    • The even subindices (2, 4, 6, ...) refer to the corresponding Y-values, i.e. the values to be mapped in each case.
    • Each X-value must be accompanied by a corresponding Y-value. Within the lookup values the signal is interpolated; above/below it is extrapolated with the last/first available slope.

Index (hex)

Name

Meaning

0x80n0:0B

Enable user lookup table

Enable lookup table

0x80n1:21

Lookup table length

Number of x/y values in the lookup table.

Maximum number of values: 40dec
(corresponds to 20 lookup values with 20x/y value pairs)

0x80n5:01

Scaler Value 1

Lookup x-value 1

0x80n5:02

Scaler Value 2

Lookup y-value 1

…

 

 

0x80n5:27

Scaler Value 39

Lookup x-value 20

0x80n5:28

Scaler Value 40

Lookup y-value 20