Technical data - Signal distribution board
Technical data | Signal distribution board |
|---|---|
PCB layer stack | Multilayer PCB, min. 4 layers |
PCB thickness | 1.6 mm ± 10 % |
Board connector | Samtec: SSQ-120-01-L-D |
Starting from the left: | |
EJ1100 (2.2 A) | |
EJ9400 (2.5 A) | |
Air gap and leakage distances between E-bus- and field signals | typ. 1.2 mm |
Differential impedance of the LVDS traces | 100 Ω |
SGND connection | via mounting bolts |
max. 100 mm | |
92 mm | |
Module depth above PCB | min. 55 mm |
Distance between PCB and mounting surface | min. 4 mm |
Standard |
Description of potential groups | |
|---|---|
UEBUS: Power supply E-bus | The power supply UEBUS is provided by the coupler and supplied from the supply voltage Us of the EtherCAT coupler. UEBUS: E-bus power supply 3.3 V GND: E-bus GND signal; |
Us: Power supply bus side | The power supply Us is used to supply the bus coupler electronics and to generate voltage for the E-bus (UEBUS). 0 V Us: Bus side GND signal 24 V Us: Bus side power supply 24 V |
Up: Power supply field side | The peripheral voltage Up supplies the electronics on the field side. 0 V Up: GND signal field side 24 V Up: Power supply field side 24 V |
SGND: Shield Ground | Ground signal with shielding function in relation to the rest of the board Notice Us, Up and SGND must not be in direct contact with each other! Connect the SGND signal directly to the mounting plate via metal bolts (see chapter SGND Connection) |
Notice | |
Damage to devices possible Note the specifications and notes for the components used! |