Infosys在阅读器中打开 / AI 翻译

EPPxxxx | Industrial housing · 0 次阅读

Underrange, Overrange

Undershoot and overshoot of the measuring range (underrange, overrange), index 0x60n0:02, 0x60n0:03

  • Uk > Ukmax: Index 0x60n0:02 and  index 0x60n0:07 (overrange and error bit) are set. The linearization of the characteristic curve is continued with the coefficients of the overrange limit up to the limit stop of the A/D converter or to the maximum value of 0x7FFF.
  • Uk < Ukmax: Index 0x60n0:01 and  index 0x60n0:07 (underrange and error bit) are set. The linearization of the characteristic curve is continued with the coefficients of the underrange limit up to the limit stop of the A/D converter or to the minimum value of 0x8000.

For overrange or underrange the red error LED is switched on.