EPxxxx | Industrial housing · 0 次阅读

Parameterization

 

Parameterization 1:

Enter alternating current data as peak values

Parameterization 2:

All alternating current data must be entered as peak values.

  • If RMS values are specified in the motor data sheet, multiply them by √2 to convert them to a peak value.
    4 Arms must be converted to 5.657 Apeak, for example.

 

Motor parameters

Set the following parameters according to the specifications in the motor data sheet:

  • 0x6075:0 "Motor rated current Ch.1": rated current in [mA] as peak value
  • 0x2003:11 "Max current": maximum current in [mA] as peak value
  • 0x2003:2E "Rated speed" rated velocity in [rpm]
  • 0x2003:13 "Motor pole pairs": the number of pole pairs of the motor

If the number of pole pairs of the motor is unknown, leave the parameter at the default value 1. The actual motor speed is then reduced by the factor "number of pole pairs" compared to the default.
After commissioning, you can determine the number of pole pairs experimentally, see chapter Determine number of pole pairs.

Further parameters

  • 0x2002:64 set "Commutation type" to "Sensorless FOC with forced startup".
  • DC link settings in CoE object 0xF800

NC scaling factors

  • Position values
    Default: 0x100000 = 1048576dec increments = 1 revolution
    Parameterization 3:
  • Velocity values
    Default: 268435 increments = 1 revolution
    Parameterization 4:
  • Torque values
    Default: 1000 increments = rated motor current