0x0000 | 0 | No error | - |
0x8001 | 32769 | The PLC function block is sending commands to an object, which is not in running state. | - |
0x8002 | 32770 | The id is out of range. | - |
0x8003 | 32771 | The type of the object is not compatible to the PLC function block. | - |
0x8004 | 32772 | Status byte of a terminal channel is not 0. | - |
0x8005 | 32773 | No data received yet. | - |
0x8006 | 32774 | Watchdog error. | - |
0x8007 | 32775 | Wrong boot configuration version. | - |
0x8008 | 32776 | Error while opening boot configuration file of the scenes on the target. | error id of FB_FileOpen() |
0x8009 | 32777 | Error while reading boot configuration file of the scenes on the target | error id of FB_FileRead() |
0x800A | 32778 | Error while writing boot configuration file of the scenes on the target. | error id of FB_FileWrite() |
0x800B | 32779 | Error while closing boot configuration file of the scenes on the target. | error id of FB_FileClose() |
0x800C | 32780 | Error while opening boot configuration file on the target. | error id of FB_FileOpen() |
0x800D | 32781 | Error while reading boot configuration file on the target. | error id of FB_FileRead() |
0x800E | 32782 | Error while writing boot configuration file on the target. | error id of FB_FileWrite() |
0x800F | 32783 | Error while closing boot configuration file on the target. | error id of FB_FileClose() |
| | | |
0x8015 | 32789 | The parameters of the sunblind object are invalid. | 1: the id of BlindDriveGroup is out of range. 2: the id of DigitalSignalGroupUp is out of range. 3: the id of DigitalSignalGroupDown is out of range. 4: the id of WeatherStation is out of range. 5: the id of RoomTemperatureSignalGroup is out of range. 6: the id of MotionDetectionDigitalSignalGroup is out of range. 7: the id of DigitalSignalGroupAutomaticOff is out of range. 8: the id of DigitalSignalGroupUpDown is out of range. |
0x8016 | 32790 | The parameters of the lamp object are invalid. | 1: MinControlValue is bigger or equal MaxControlValue. 2: FadeSteps is bigger or equal (MaxControlValue - MinControlValue). 3: the id of DALILine is out of range. 4: DALIShortAddress is out of range.
|
0x8017 | 32791 | The parameters of the lighting object are invalid. | 1: the id of ActualValueSignalGroup is out of range. 2: the id of LampGroup is out of range. 3: the id of DigitalSignalGroupDimmUp is out of range. 4: the id of DigitalSignalGroupDimmDown is out of range. 5: the id of DigitalSignalGroupDimmUpDown is out of range. 6: the id of DigitalSignalGroupMotionDetection is out of range. 7: the id of DigitalSignalGroupMotionDetection is 0. 8: PresenceValue is below 0. 9: ProlongValue is below 0. 10: the id of ActualValueSignalGroupId is out of range. 11: the id of ActualValueSignalGroupId is 0. 12: calculated lower point of hysteresis (BasicSetpointValue + SetpointValueShift - ControlHysteresis / 2) is below 0. 13: SwitchOnLevel is below 0. 14: SetpointValueShiftStepSize is below 0. 15: MaximalSetpointValueShift is below MinimalSetpointValueShift. 16: the id of LampGroupSub1Id is out of range. 17: the id of LampGroupSub2Id is out of range. 18: FactorControlValueSubLampGroup1 is below 0. 19: FactorControlValueSubLampGroup2 is below 0. 20: MaxControlDelay is below the minimum of t#1s. 21: ControlHysteresis is below 0. 22: ControlOnUpperLimit is below or equal to 0. 23: the id of WeatherStation is out of range. 24: the id of WeatherStation is 0. |
0x8018 | 32792 | The parameters of the HVAC object are invalid. | 1: the id of AnalogSignalGroupRoomTemperature is out of range. 2: the id of AnalogSignalSetpointValueShift is out of range. 3: the id of DigitalSignalGroupDewPoint is out of range. 4: the id of DigitalSignalGroupWindowContact is out of range. 5: the id of DigitalSignalGroupMotionDetection is out of range. 6: - 7: - 8: the id of ValveActuatorGroupHeating2Point is out of range. 9: the id of ValveActuatorGroupCooling2Point is out of range. 10: the id of ValveActuatorGroupHeatingContinuous is out of range. 11: the id of ValveActuatorGroupCoolingContinuous is out of range. 12: the id of WeatherStationOutdoorTemperature is out of range. 13: the parameter SummerCompensationStartLevel >= SummerCompensationEndLevel. 14: the parameter SummerCompensationGradient is out of range. 15: the setpoint values are invalid. 16: the parameter PWMPeriodDurationCooling is out of range. 17: the parameter PWMPeriodDurationHeating is out of range. 18: the parameter YMinPIDCooling is out of range. 19: the parameter YMaxPIDCooling is out of range. 20: the parameter YMinPIDCooling >= YMaxPIDCooling. 21: the parameter YMinPIDHeating is out of range. 22: the parameter YMaxPIDHeating is out of range. 23: the parameter YMinPIDHeating >= YMaxPIDHeating. |
0x8019 | 32793 | The parameters of the analog signal object are invalid. | 1: EnOceanMappingListItem is out of range. 2: EnOceanDataByte is out of range. 3: the id of DALILine is out of range. 4: the DALIShortAddress is out of range. 5: the id of EnOceanLine is out of range. |
0x801A | 32794 | The parameters of the digital signal object are invalid. | 1: EnOceanMappingListItem is out of range. 2: EnOceanDataByte is out of range. 3: EnOceanDataBit is out of range. 4: the id of EnOceanLine is out of range. 5: the id of DALILine is out of range. 6: the DALIShortAddress is out of range. |
0x801B | 32795 | The signal object of the actual value is in error state. | - |
0x801C | 32796 | The signal object of the dew point value is in error state. | - |
0x801D | 32797 | The parameters of the window object are invalid. | 1: the id of WindowDriveGroup is out of range. 2: the id of DigitalSignalGroupClose is out of range. 3: the id of DigitalSignalGroupOpen is out of range. |
0x801E | 32798 | The DALI Ballast is in error state. | - |
0x801F | 32799 | The KL3403 is in error state. | 0x100: timeout Error. The allowed execution time elapsed. 0x200: parameter Error (e.g. at an incorrect register number). 0x300: the gathered value differs from the written value (write access to this register is possibly not allowed or has failed). |
0x8020 | 32800 | The parameters of the iFront blind drive object are invalid. | - |
0x8021 | 32801 | Overload - LagDistance greater than allowed. | - |
0x8022 | 32802 | Encoder doesn't count. | - |
0x8023 | 32803 | Drive not calibrated (at start to target position). | - |
0x8024 | 32804 | Terminal not ready. | - |
0x8025 | 32805 | Error of terminal. | - |
0x8026 | 32806 | The parameters of the time scheduler channel object are invalid. | 1: periodicity is equal to 0 or greater than 365. 2: periodicity is equal to 0 or greater than 52. 3: no weekday selected. 4: a switching event within the next 1500 days cannot be determined. 5: periodicity is equal to 0 or greater than 31. 6: no month selected. 7: periodicity is equal to 0 or greater than 4. 8: the initial day is equal to 0 or greater than 365. 9: the initial week is equal to 0 or greater than 52. |
0x8027 | 32807 | The parameters of the weather station object are invalid. | 1: the id of AnalogSignalTemperature is out of range. 2: the id of AnalogSignalWindSpeed is out of range. 3: the id of AnalogSignalBrightnessEast is out of range. 4: the id of AnalogSignalBrightnessSouth is out of range. 5: the id of AnalogSignalBrightnessWest is out of range. 6: the id of AnalogSignalDaylight is out of range. 7: the id of AnalogSignalRain is out of range. 8: the id of AnalogSignalRelativeHumidity is out of range. 9: the id of SerialCommunicationLine is out of range. |
0x8028 | 32808 | Errror accessing the DALI ballast. | 1: no answer from the DALI terminal. 2: no answer from the DALI ballast. 3: communication buffer overflow. 4: no answer from the communication block. 5: DALI collision detected on the backward channel: During the transfer of a DALI telegram, a collision with the send data of another DALI slave was detected. 6: DALI collision detected on the forward channel: During the transfer of a DALI telegram, a collision with the send data of another DALI master was detected. 7: Overload of the internal DALI power supply unit of the KL6811 (bus under-voltage). |
0x8029 | 32809 | Error during receiving data from weather station. | 1: watchdog. 2: dataframe has wrong length. 3: error Checksum. |
0x802A | 32810 | The parameters of the composition module object are invalid. | 1: the id of DigitalSignalPushButton is out of range. 2: the id of LampFeedbackLED is out of range. 3: the id of Lighting is out of range. 4: the id of SunblindWindow is out of range. 5: the id of Scene is out of range.. |
0x802B | 32811 | The parameters of the blind drive object are invalid. | 1: the id of DigitalSignalGroupLockDriveDown is out of range. |
0x802C | 32812 | Terminal is not initialized. | - |
0x802D | 32813 | Direction of rotation of motor is wrong. Check wiring. | - |