ED407x | EtherCAT Terminals, analog output, multi-function, ±10 V, ±20 mA, 16 bit, single-ended, 2 ksps, push-in · 0 次阅读

Interface

The interface setting is fundamental for operation as an electrical output.

Setting: CoE 0x80nD:11 Output interface

Setting

Measuring range

None

-

V

±10 V

V

0-10 V

I

±20 mA

I

0-20 mA

I

4-20 mA

Note: When the interface is changed, the following CoE parameters of UserScale, Warning Level, Limiter, Output SlewRate, Watchdog are reset to the default setting.