0 | No Error: Station is in data exchange. |
1 | Station deactivated: The slave has been deactivated. |
2 | Station not exists: Slave does not respond. Check whether the slave is switched on, the cabling is correct or the address is correct. |
3 | Master lock: The slave is exchanging data with another master. |
4 | Invalid slave response: An incorrect response from the slave. Occurs temporarily if the slave has terminated the data exchange due to a local event. |
5 | Parameter fault: Indicates a parameterization error. |
6 | Not supported: A DP function is not supported. Check whether the GSD file and the address is correct. |
7 | Config fault: Indicates a configuration error. Check whether the added terminals or modules are OK. |
8 | Station not ready: The device is starting up. This is displayed temporarily during startup. |
9 | Static diagnosis: The slave indicates a static diagnosis and is currently unable to provide valid data. Check the operating state at the slave. |
10 | Diagnosis overflow: The slave indicates a diagnosis overflow. Read the diagnostics data with ADS Read and check the operating state of the slave. |
11 | Physical fault: Indicates a physical error in the response of a slave. Check the cabling. |
12 | Data-Exchange left: The data transmission was not completed. |
13 | Severe bus fault: Indicates a severe bus fault. Please check the cabling. |
14 | Telegram fault: The slave responds with an invalid telegram. |
15 | Station has no ressources: The slave does not have enough resources for the telegram. Check whether the GSD file is correct. |
16 | Service not activated: Occurs if the slave terminates the data exchange due to a local event. Check whether DP functionality is disabled for the slave. |
17 | Unexpected telegram: Unexpected telegram, can occur temporarily if two PROFIBUS networks are plugged together or check whether bus times are set the same for the second master. |
18 | Station ready: Occurs temporarily during startup and as long as the task has not yet started. |
31 | only for EtherCAT gateways: WC state of the cyclic EtherCAT frame is 1. |
128 | Slave waiting for data transfer: The slave has been parameterized and configured, but has not yet received a Data_Exchange telegram. |
129 | Slave waiting for configuration: The slave has been parameterized but has not yet received a Chk_Cfg telegram. |
130 | Slave waiting for parameter: Slave has not yet been parameterized and is waiting for Set_Prm (Lock) telegram. |
131 | Slave waiting for baud rate: The baud rate has not been set. |
132 | Slave waiting for station no. from PLC: The Profibus address has not been set. |