Infosys在阅读器中打开 / AI 翻译

ED336x-0x00 | EtherCAT Terminals, 2-channel analog input, measuring bridge, full bridge, 24 bit, push-in · 0 次阅读

Wiring with push-in connection technology EC/ED/EFxxxx

WARNING

Risk of electric shock and damage of device!

Bring the bus terminal system into a safe, powered down state before starting installation, disassembly or wiring of the bus terminals!

Wiring with push-in connection technology EC/ED/EFxxxx 1:Fig.18: Wiring and disconnecting the conductors
1. Connect solid conductors and conductors with ferrules (Fig. top left, step 2)
These can be connected using the direct plug-in technique without tools.
  • Insert the conductor into the terminal point after stripping the insulation (2)
2. Connect fine-stranded cables (Fig. top right, steps 1 - 3)
These must be connected via the push-button.
  • Use a screwdriver to press the push-button to open the contact point (1).
  • Then insert the conductor (2).
  • Release the push-button by pulling back the screwdriver to close the terminal point (3).

Release cables (Fig. above steps 4 - 6)
The release is carried out for all conductor types using the push-button.

  • Use a screwdriver to press the push-button to unlock the contact (4).
  • Then pull out the conductor (5).
  • Release the push-button by pulling back the screwdriver to close the terminal point (6).

Notice

Wiring with push-in connection technology EC/ED/EFxxxx 2:

Observe the permissible connection cross-sections and strip lengths

The permissible conductor cross-section and strip length depend on the type of housing, please refer to the housing data in the "Technical data" chapter for the device in question.