Cabling

Guidelines

Follow these guidelines to ensure IP67 protection:

  • Mount plugs with the torque values specified below. Use a torque wrench, e.g. Beckhoff ZB8801.
  • Seal unused connectors with protective caps.
  • Ensure the correct seating of pre-assembled protective caps.
    Protective caps are pre-assembled at the factory to protect connectors during transport. They may not be tight enough to ensure IP67 protection.

Connector overview

Note

Risk of confusion: Inputs and outputs

Defects possible due to mixing up of inputs and outputs. The connectors of the inputs and outputs are of the same type.

  • Observe the names of the connectors in order to avoid mistakes.
Cabling 1:
Connector overview

Name

Connector
type

Tightening
torque

Function

X01

M12

0.6 Nm

Analog inputs

X02

X03

M12

0.6 Nm

Analog outputs

X04

X50

M8 socket, p-coded

0.4 Nm

EtherCAT P input

X51

M8 socket, p-coded

0.4 Nm

EtherCAT P downstream connection

Further Information