Connection example - wiring in series without AX bridge
Wire the relevant connections using individual cables.
CAUTION
Damage to persons and devices!
Please ensure that the final supply network connection cable is adequately dimensioned. The dimensioning depends on the sum current and must comply with EN60204-1.
To create a DC link group wire the X02 connections with a suitable cable. Voltages up to 890 V may be present.
The connectors are designed for a maximum current of 41 A and a maximum conductor cross-section of 6 mm².
Avoid phase reversal between the devices!
No UL drive system!
The following figure shows an AX wiring in series configuration without AX Bridge. To configure a UL drive system, please refer to the information in chapter "UL drive system – configuration example".