Infosys在阅读器中打开 / AI 翻译

EPxxxx | Industrial housing · 0 次阅读

Cabling

Guidelines

Follow these guidelines to ensure IP67 protection:

  • Mount plugs with the torque values specified below. Use a torque wrench, e.g. Beckhoff ZB8801.
  • Seal unused connectors with protective caps.
  • Ensure the correct seating of pre-assembled protective caps.
    Protective caps are pre-assembled at the factory to protect connectors during transport. They may not be tight enough to ensure IP67 protection.

Connector overview

Cabling 1:
Connector overview

Name

Function

Connector type

Tightening torque

1

Analog inputs

M12 socket

0.6 Nm 1)

2

3

Analog outputs

M12 socket

0.6 Nm 1)

4

X40

EtherCAT input

M8 socket

0.4 Nm 1)

X41

EtherCAT-Weiterleitung

M8 socket

0.4 Nm 1)

X60

Supply voltage input

M8 plug connector

0.4 Nm 1)

X61

Supply voltage downstream connection

M8 socket

0.4 Nm 1)

Further Information