Infosys在阅读器中打开 / AI 翻译

SCL6xxx | Low power split-core transformers, 3-channel current interface, accuracy class 0.5, electronic nameplate, RJ45 · 0 次阅读

Maintenance, inspection and troubleshooting

DANGER

Dangerous electrical voltage leads to electric shock and arc flashover!

Non-compliance will result in death, personal injury or considerable material damage!
Ensure a safe working environment during assembly, maintenance and installation work

  • Before beginning any assembly, maintenance, or installation work, disconnect the system from the power supply!
  • Interrupt the power supply of the primary conductor and secure against being switched on again inadvertently.
  • Make sure that the details on the nameplate and in the “Technical data” correspond to the operating parameters of the system.

Maintenance and inspection

  • Check whether the secondary conductors are firmly connected to the measuring device.
  • Check whether the current transformer is closed correctly.
  • Remove coarse dirt from the housing of the current transformer.
  • Contact with moisture, in particular with the core, must be avoided at all costs.

Troubleshooting

In the case of errors, e.g. unexpected or incorrect values, inverse power:

  • Check the settings of the measuring device on the basis of its operating instructions.
  • Check whether the current transformer is mounted on the intended conductor in the direction of the energy flow.
  • Check the connection of the current transformers and the corresponding voltage tap-off if the active and/or reactive power does not correspond to the expected values; if necessary, one phase has been reversed.
  • Check whether the current transformer is connected correctly.
  • Check the power requirement of the conductors and measuring devices connected to the current transformer. It must not exceed the rated power of the current transformer (see name plate).
  • If the above points do not solve the problem:
    Check whether there is dust or other dirt between the two parts of the core. If so, clean the surfaces carefully with a lint-free cloth.
  • Avoid hand contact (sweat)!