BC9000 and BC9100 | Bus Terminal Controller for Ethernet · 0 次阅读

Preset single register (Function 6)

The function Preset singles register can be used to access the output or flag process image (only for controllers) and the Modbus TCP interface.

Function 6 writes the first output word. The outputs start at an offset of 0x0800. Here again the offset always describes a word. This means offset 0x0803 refers to the fourth word in the output process image.

Query

Byte name

Sample

Function code

6

Start address high

8

Start address low

0

Data high

63

Data low

255

The Fieldbus Coupler replies with the same telegram and confirmation of the received value.

Response

Byte name

Sample

Function code

6

Start address high

8

Start address low

0

Data high

63

Data low

255